Alarm Drop #123 - Exhaust Thermocouple Trouble
(alone - no other Combustion Monitor Alarms) Signal Name: L30SPTA Alarm occurs when the difference between the highest and lowest TC is greater than 5x (five times) the internally calculated Combustion Monitor Allowable Spread. Check for Smoke! If YES: initiate trip. If NO:
Note, combustion monitor spreads are determined in SEQ_TRB2, Rung -86. If defective TC, replace faulty TC at first opportunity. Home | About Us | Contact Us | Documentation Services | HPC Employees HPC Technical Services, 500 Tallevast Road - Suite 101, Sarasota, FL 34243 USA |
|